GB Operating Manual Light control “PULSE HFMD - Vers. III“
GB Operating Manual Light control “PULSE HFMD - Vers. III“
LED 1 2 3 4 5 6
Fig. 6
Change basic settings - Level 3
Activate setting level 3 (function 30)
Logo fl ashes white
Sensor LEDs fl ash blue
Actuation
Display
Press both keys
until the logo switches from
ashing to OFF and from OFF
again to fl ashing.
Change function Increase presence range
Briefl y press key I
The light bar shows the newly
set presence range.
- Level 1 LED 1 10 %
- Level 2 LED 1-2 20 %
- Level 3 LED 1-3 40 %
- Level 4 LED 1-4 60 %
- Level 5 LED 1-5 80 %
- Level 6 LED 1-6 100 %
Change function Reduce presence range
Briefl y press key II
The light bar shows the newly
set presence range.
Fig. 3
Key I
Logo
Light
bar
Key II
LED I
LED II